3512B Diesel Generator Set

3512B Diesel Generator Set

360° Exterior View

The 3512B generator set has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can ...
PDF Print Share

Generator Set Specifications

Standby Rating
1625/1600/1500 kVA
Prime Power Rating
1500/1360 kVA
Emissions/Fuel Strategy
Low Fuel , Low Emissions
Voltage
400 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous
Minimum Rating
1360 kVA
Maximum Rating
1625 kVA

Engine Specifications

Engine Model
3512B TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
6.69in
Stroke
7.48in
Displacement
3161.03in³
Compression Ratio
14.0:1
Aspiration
TA
Fuel System
Electronic Unit Injection
Governor Type
ADEM™ A3

Generator Set Dimensions

Length - Minimum
212.8in
Length - Maximum
217.1in
Width - Minimum
90in
Width - Maximum
90in
Height - Minimum
94.9in
Height - Maximum
94.9in
Dry Weight - Genset (minimum)
25620lb
Dry Weight - Genset (maximum)
26530lb

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • Eurasian Conformity (EAC)
  • Telecommunication Lab of China

One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment:

Optional Equipment:

    Air Inlet System
    • Heavy duty air cleaner
    • Dual element air cleaner
    • Single element filter
    Exhaust
    • Exhaust mufflers
    Generator
    • Internal excitation (IE)
    • Oversize and premium generators
    • Permanent magnet excitation (PMG)
    • Anti-condensation heater
    Control System
    • Generator temperature monitoring
    • Neutral to ground connection
    • Local annunciator modules (Low voltage)
    • EMCP 4.3, EMCP 4.4
    • Cat connect: Ethernet telematics / Satellite telematics / Cell telematics
    • Annunciator modules (Local and remote)
    • Load share module options (LV)
    • CAN2 network equipment
    • Governors (MUI-Low voltage)
    • Customer interface options
    • Annunciator network equipment
    • Remote annunciator module (Low voltage)
    • EMCP voltage and current sensing groups
    Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
    Cooling System
    • Installed radiators
    • Cooling system attachments
    • Water level switch gauges
    • Coolant
    Mounting
    • Rubber anti-vibration mounts
    • IBC isolators
    • Spring type vibration isolators
    Starting/charging
    • Charging alternator
    • Heavy duty starting system
    • Oversize batteries
    • Air starting motor with control and silencer
    • Jacket water heater
    • Battery chargers
    Exhaust System
    • Y Adapters
    • Mufflers
    • Flexible fittings
    • Flange and exhaust expanders
    • Elbows
    Factory Support
    • Factory commissioning
    Fuel System
    • Primary fuel filter
    • Secondary fuel filters
    Generators And Attachments
    • Low voltage generators 380, 400, 415 Volts 3 Phase, 1500 rpm
    • Space heater kit
    • 1400 and 1600 Frame
    • Pitch 0.6667
    • 6 Leads
    • Internally excitation
    • Generator conversion kits - PM to IE / IE to PM
    • Permanent magnet excitation (PMG)
    • RW
    General
    • UL 2200 package
    • The following options are based on regional and product configuration:
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
    • EU Certificate of Conformance (CE)
    Instrumentation
    • Pyrometer and thermocouples
    Lube System
    • Drain GP oil pan
    • Lube oil filters
    • Oil level regulator
    • Standard sump oil pan
    • Lube oil in standard sump
    • Prelube pump groups
    Crankcase System
    • Crankcase protection group
    • Crankcase ventilation system
    Mounting System
    • Low efficiency isolators
    • Spring type vibration isolators
    • Low efficiency isolators puck
    • Low isolators
    Power Connections
    • Low voltage - Package mounted circuit breakers
    • Electrically operated circuit breakers
    • Low voltage - 1400 and 1600 Frame generators
    • Low voltage - Power connection options
    Special Tests / Reports
    • Standard generator TVA report
    • Standard engine test charge
    • Generator test report
    • PGS Test report @ 1.0 power factor
    • Custom generator TVA report
    • Generator fuel consumption test
    • PGS Test report @ 0.8 power factor
    Starting / Charging System
    • Batteries, racks and cables
    • 10 Amp Battery charger
    • Starter cover
    • Electric starting motors
    • Jacket water heaters
    • 20 Amp Battery charger
    • Jacket water heater wiring groups
    • 35 Amp Battery charger
    Extended Service Coverage
    • Silver - 36 ,48, 60, 120 month coverage
    • Gold - 36,48, 60, 120 month coverage
    • Cat branded commercial power system