3512B Diesel Generator Set
1600 - 1875 kVA at 50 Hz Diesel GensetThe 3512B generator set has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters
...1600 - 1875 kVA at 50 Hz Diesel Genset
The 3512B generator set has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance that matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.
Q. Does this generator comply with ISO 8528 guidelines?
A. Yes, the 3512B, like all of our generators, is tested in accordnace the load steps outlined in with ISO 8528, Part 5.
Generator Set Specifications
- Standby Rating
-
1875/1750 kVA
- Prime Power Rating
-
1700/1600 kVA
- Emissions/Fuel Strategy
-
Low Fuel , Low Emissions
- Voltage
-
400 to 415 Volts
- Frequency
-
50 Hz
- Speed
-
1500 rpm
- Duty Cycle
-
Standby, Mission Critical, Prime, Continuous
- Minimum Rating
-
1600 kVA
- Maximum Rating
-
1875 kVA
Engine Specifications
- Engine Model
-
3512B TA, V-12, 4-Stroke Water-Cooled Diesel
- Bore
-
6.69in
- Stroke
-
7.48in
- Stroke - HD
-
8.46in
- Displacement
-
3161.03in³
- Displacement - HD
-
3576in³
- Compression Ratio
-
15.5:1 HD
- Aspiration
-
TA
- Fuel System
-
Electronic Unit Injection
- Governor Type
-
ADEM™ A3
Generator Set Dimensions
- Length - Minimum
-
212.8in
- Length - Maximum
-
217.1in
- Width - Minimum
-
90in
- Width - Maximum
-
90in
- Height - Minimum
-
94.9in
- Height - Maximum
-
94.9in
- Dry Weight - Genset (minimum)
-
25620lb
- Dry Weight - Genset (maximum)
-
26530lb
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
EMCP 4 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- EU Declaration of Conformity
- EU Declaration of Incorporation
- Eurasian Conformity (EAC)
- Telecommunication Lab of China
One Safe Source
- Components used in the generator set are selected at the design stage to provide optimum package performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment:
- Control System
-
- EMCP 4.2B
- Emergency stop pushbutton
- Failure to start (overcrank)
- High coolant temperature
- 4 Programmable digital outputs
- Auto/start/stop control
- 4 Programmable digital inputs
- DC volts
- Engine cycle crank
- Low coolant level
- Speed adjust
- Low oil pressure
- Communications
- Frequency (Hz)
- Warnings/shutdown indicators
- Engine cool-down timer
- Operating hours
- Emergency stop
- Oil pressure
- Lamp test
- True RMS AC metering, 3-phase, +/-2% accuracy
- Digital indication for:
- Overspeed
- Alarm acknowledge
- RPM
- 24 Volt DC operation
- Amps (per phase & average)
- Coolant temperature
- Volts (L-L & L-N)
- Cooling System
-
- SCAC
- Coolant drain line with valve
- Radiator fan and fan drive
- Fan and belt guards
- Coolant level sensors
- Caterpillar extended life coolant
- Exhaust System
-
- Dry exhaust manifold
- Flanged faced outlet(s)
- Fuel System
-
- Fuel cooler; not included with packages without radiator
- Flexible fuel lines
- Secondary fuel filters.
- Fuel priming pump
- Generator System
-
- RFI suppression
- Min / max exciter
- 3 phase brushless, Salient pole
- Caterpillar's digital voltage regulator (CDVR)
- Class H temperature rise at 40C ambient
- Random wound
- Winding temperature detectors
- Internal excitation (IE)
- 3 Phase voltage sensing
- Busbar connections
- 6 Leads
- NEMA Class H insulation
- Literature
-
- Parts book
- Operation & Maintenance Manual
- Lube System
-
- Lubricating oil
- Gear type lube oil pump
- Fumes disposal
- Oil drain lines and valve
- Oil filter, filler and dipstick
- Integral lube Oil cooler
- Mounting System
-
- Rails - Engine/generator/radiator mounting
- General
-
- Flywheel and Flywheel housing-SAE
- Caterpillar yellow with high gloss black rails & radiator
- RH service
- SAE standard rotation
Optional Equipment:
- Air Inlet System
-
- Dual element air cleaner
- Single element filter
- Heavy duty air cleaner
- Generator
-
- Internal excitation (IE)
- Oversize and premium generators
- Anti-condensation heater
- Permanent magnet excitation (PMG)
- Control System
-
- EMCP voltage and current sensing groups
- CAN2 network equipment
- Annunciator modules (Local and remote)
- Customer interface options
- Load share module options (LV)
- EMCP 4.3, EMCP 4.4
- Annunciator network equipment
- Neutral to ground connection
- Generator temperature monitoring
- Remote annunciator module (Low voltage)
- Local annunciator modules (Low voltage)
- Cat connect: Ethernet telematics / Satellite telematics / Cell telematics
- Governors (MUI-Low voltage)
- Power Termination
-
- Circuit breakers, IEC compliant
- Circuit breakers, UL listed
- Cooling System
-
- Installed radiators
- Coolant
- Water level switch gauges
- Cooling system attachments
- Mounting
-
- IBC isolators
- Rubber anti-vibration mounts
- Spring type vibration isolators
- Starting/charging
-
- Jacket water heater
- Oversize batteries
- Battery chargers
- Charging alternator
- Heavy duty starting system
- Air starting motor with control and silencer
- Exhaust System
-
- Flexible fittings
- Mufflers
- Y Adapters
- Elbows
- Flange and exhaust expanders
- Fuel System
-
- Secondary fuel filters
- Primary fuel filter
- Generators And Attachments
-
- Internally excitation
- Permanent magnet excitation (PMG)
- RW
- 6 Leads
- Space heater kit
- 1400 and 1600 Frame
- Pitch 0.6667
- Low voltage generators 380, 400, 415 Volts 3 Phase, 1500 rpm
- Generator conversion kits - PM to IE / IE to PM
- General
-
- EU Certificate of Conformance (CE)
- The following options are based on regional and product configuration:
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- UL 2200 package
- Instrumentation
-
- Pyrometer and thermocouples
- Lube System
-
- Lube oil in standard sump
- Standard sump oil pan
- Lube oil filters
- Drain GP oil pan
- Oil level regulator
- Prelube pump groups
- Crankcase System
-
- Crankcase protection group
- Crankcase ventilation system
- Mounting System
-
- Low efficiency isolators
- Low efficiency isolators puck
- Low isolators
- Spring type vibration isolators
- Power Connections
-
- Low voltage - Power connection options
- Electrically operated circuit breakers
- Low voltage - Package mounted circuit breakers
- Low voltage - 1400 and 1600 Frame generators
- Special Tests / Reports
-
- Custom generator TVA report
- PGS Test report @ 1.0 power factor
- Generator fuel consumption test
- Standard generator TVA report
- PGS Test report @ 0.8 power factor
- Generator test report
- Standard engine test charge
- Starting / Charging System
-
- 20 Amp Battery charger
- 10 Amp Battery charger
- Electric starting motors
- Starter cover
- Batteries, racks and cables
- Jacket water heater wiring groups
- Jacket water heaters
- 35 Amp Battery charger
- Extended Service Coverage
-
- Gold - 36,48, 60, 120 month coverage
- Cat branded commercial power system
- Silver - 36 ,48, 60, 120 month coverage
- Platinum - 24, 36, 48, 60, 120 month coverage