3516 Diesel Generator Set

3516 Diesel Generator Set

The 3516 generator set has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can ...
PDF Print Share

Generator Set Specifications

Standby Rating
1750 ekW
Prime Power Rating
1600 ekW
Emissions/Fuel Strategy
Low Fuel, Low Emissions
Voltage
380 to 13800 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous
Maximum Rating
1750 ekW
Minimum Rating
1450 ekW

Engine Specifications

Engine Model
3516 TA, V-16, 4-Stroke Water-Cooled Diesel
Bore
6.69in
Stroke
7.48in
Displacement
4210.64in³
Compression Ratio
13.0:1
Aspiration
TA
Fuel System
Mechanical unit injection
Governor Type
Woodward

Generator Set Dimensions

Length - Maximum
247in
Width - Maximum
90in
Height - Maximum
94.9in
Dry Weight - Genset (maximum)
28840lb

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • UL 2200 Listed
  • CSA
  • IBC seismic certification
  • OSHPD pre-approval

One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment:

Optional Equipment:

    Control System
    • Controller: EMCP 4.2B
    • Local annunciator module: [ ] NFPA 110 [ ] Custom
    Air Inlet System
    • Dual element air cleaner
    • Single element filter
    Cooling System
    • Standard ambient radiators
    • Coolant
    • Optional installed ATAAC radiators
    • Optional installed radiators
    • Water level switch gauges
    • Standard ambient ATAAC radiators
    Engine Options
    • Starting motors: [ ] Standard [ ] Heavy duty
    • Batteries: [ ] Standard (1400 CCA) [ ] Heavy Duty (2800 CCA)
    • Starting aids: [ ] 220V 50 Hz Jacket water heater
    • Battery charger: [ ] 10A [ ] 20A [ ] 35A
    • Air cleaner: [ ] Single element air cleaners [ ] Dual element air cleaners [ ] Heavy duty air cleaners
    • Muffler: [ ] Industrial Grade
    Crankcase System
    • No explosion relief valves
    • Ventilation system
    • Explosion relief valves
    Alternators
    • Temperature rise (over 40°C ambient): [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C
    Exhaust System
    • Y Adapters
    • Tier 4 clean emissions module
    • Tier 4 dosing cabinet
    • Elbows
    • Tier 4 clean emission MOD Kits
    • Exhaust offset
    • Flanges
    • Flange and exhaust expanders
    • Flexible fittings
    • Mufflers
    • Clean emission parts
    Fuel System
    • Fuel priming pumps (Tier 4) - Manual or electric
    • Primary fuel filter
    General
    • US aid emblem
    • Special paint (Colors other than Caterpillar yellow or high performance paints)
    • The following options are based on regional and product configuration:
    • UL 2200 package
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
    Generators And Attachments
    • High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
    • Generator conversion
    • Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
    • Thermostat for space heater
    • Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
    • Alternator air cleaner
    • Differential current transformers (DCT)
    • High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
    • Differential current transformers (DCT) 8.7 kV and 15 kV classes
    • Space heater kit
    Power Termination
    • Circuit breaker operation: [ ] Electrical
    • Circuit breaker rating: [ ] 2000A [ ] 2500A [ ] 3200A [ ] 4000A
    • Circuit breaker trip unit: [ ] LSI [ ] LSIG [ ] LSIG-P
    • Power termination: [ ] Busbar [ ] Circuit breaker
    Extended Service Contract (esc)
    • Extended Service Contract (ESC): [ ] 2 Year [ ] 3 Year [ ] 5 Year
    Instrumentation
    • Pyrometer and Thermocouples
    Lubrication System
    • Lube oil in standard sump
    • Prelube pumps
    • Oil level regulator
    Mounting System
    • Puck style low efficiency isolators
    • Spring type vibration isolators
    • IBC vibration isolators
    Power Connections
    • Ground cables between generator and terminal box
    • Neutral ground connections
    • 2700 Frame, four lead, four terminal
    • Rear power connections
    • Right side power connections
    • Left side power connections
    • Low voltage Circuit breakers
    • Center post busbars
    Special Tests / Reports
    • Generator test report
    • OSHPD Certification
    • Canadian Standards Association certification
    • PGS Test report @ 1.0 power factor
    • IBC Certification
    • Fuel consumption test
    • Generator set fuel consumption test
    • PGS Test report @ 0.8 power factor
    • Standard engine test charge
    • Torsional vibration analysis reports
    Starting And Charging
    • Electric starting motors
    • Air pressure regulator
    • Starter cover
    • Air starting motors
    • 24 Volt battery set - Dry
    • 10, 20, 35 and 50 Amp Battery chargers
    • Jacket water heaters
    • Engine barring device
    Extended Service Coverage
    • Platinum, Gold and Silver coverage