3516C (50 Hz) with Upgradeable Package
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
- Standby Rating
-
2750 kVA
- Prime Power Rating
-
2500 kVA
- Emissions/Fuel Strategy
-
Low Fuel Consumption
- Voltage
-
380 to 11000 volts
- Frequency
-
50 Hz
- Speed
-
1500 rpm
- Duty Cycle
-
Standby, Mission Critical, Prime
- Maximum Rating
-
2750 kVA
- Minimum Rating
-
2500 kVA
Engine Specifications
- Engine Model
-
3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
- Bore
-
6.69in
- Stroke
-
8.46in
- Displacement
-
4765in
- Compression Ratio
-
14:01
- Aspiration
-
TA
- Fuel System
-
Electronic unit injection
- Governor Type
-
Adem™3
Generator Set Dimensions
- Length - Maximum
-
228.3in
- Width - Maximum
-
75.9in
- Height - Maximum
-
80.7in
- Dry Weight - Genset (maximum)
-
32404lb
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
EMCP 4 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- EU Declaration of Conformity
- EU Declaration of Conformity
- Eurasian Conformity (EAC)
- Telecommunication Lab of China
One Safe Source
- Components used in the generator set are selected at the design stage to provide optimum package performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment:
- Air Inlet System
-
- Air cleaner
- Single element canister type with service indicator
- Control Panel
-
- RPM
- Engine cycle crank
- Failure to start (overcrank)
- Warning/shutdown with common LED indication of shutdowns for:
- Speed adjust
- True RMS AC metering, 3-phase, +/-2% accuracy
- Accessory module data link
- Overcurrent (50/51)
- DC volts
- Controls:
- Generator phase sequence
- Low oil pressure
- 2 Programmable digital outputs
- Reverse power (kW) (32)
- Low coolant level
- Operating hours
- Frequency (Hz)
- kVAr-hr (total)
- kVA (per phase, average & percent)
- Lamp test
- Over/under frequency (81 o/u)
- 6 programmable digital inputs
- 2 Programmable relay outputs (Form C)
- 24 Volt DC operation
- Customer data link (Modbus RTU)
- EMCP 4 Genset controller
- Volts (L-L & L-N)
- High coolant temperature
- Alarm acknowledge
- Oil pressure (psi, kPa or bar)
- 4 Programmable relay outputs (Form A)
- Overspeed
- EMCP4.2B controller includes:
- Engine cool-down timer
- Panel lights
- kW (per phase, average & percent)
- Low coolant temperature
- Over/under voltage (27/59)
- Serial annunciator module data link
- Generator mounted - rear facing
- Communications:
- kVAr (per phase, average & percent)
- Digital indication for:
- Text alarm/event descriptions
- EMCP 4.2B
- Coolant temperature
- Emergency stop pushbutton
- Programmable protective relaying functions:
- kW-hr (total)
- Reverse reactive power (kVAr) (32RV)
- Amps (per phase & average)
- Environmental sealed front face
- Power factor (per phase & average)
- Fuel
-
- Primary fuel filter with integral water separator
- Generator
-
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
- Starting/charging
-
- Heavy duty starting system
- Charging alternator
- Cooling System
-
- Fan and belt guards
- Coolant drain line with valve
- JWAC
- Caterpillar extended life coolant
- Coolant level sensors
- Radiator fan and fan drive
- Exhaust System
-
- Flanged faced outlet(s)
- Dry exhaust manifold
- Fuel System
-
- Flexible fuel lines - shipped loose
- Fuel priming pump
- Fuel cooler; not included with packages without radiator
- Secondary fuel filters
- Generators And Attachments
-
- NEMA Class H insulation system, Class H temperature rise at 40C ambient
(125C prime / 150C standby).
- Busbar connections, top center mounted, top cable entry
- Random wound
- 6 Lead
- Winding temperature detectors
- IEC standard hole pattern
- Internal excitation (IE)
- 3 phase brushless, Salient pole
- Generator set packages include Caterpillar's digital voltage regulator (CDVR). CDVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter
- Literature
-
- Parts book
- Operation & Maintenance Manual
- Lube System
-
- Gear type lube oil pump
- Integral lube Oil cooler
- Fumes disposal
- Lubricating oil
- Oil filter, filler and dipstick
- Oil drain lines and valve
- Mounting System
-
- Rails - Engine/generator/radiator mounting
- Rubber anti-vibration mounts - shipped loose
- Starting / Charging System
-
- 24 Volt electric starting motor
- Battery and battery rack w/cables
- Battery disconnect switch
- General
-
- Right hand servicing
- Flywheel and flywheel housing-SAE No. 00
- Paint - Caterpillar yellow with high gloss black rails & radiator
- SAE standard rotation
Optional Equipment:
- Air Inlet System
-
- Remote air inlet adapters
- Dual element air cleaners
- Air inlet protection
- Heavy duty air cleaners
- Circuit Breakers
-
- Cable entry options
- Control packaging for enclosures
- Trip units
- Load take off; IEC standard hole
- Busbar power connections
- Center posts busbars
- EMAX breakers
- Power Termination
-
- Circuit breakers, IEC compliant
- Control Panels
-
- Annunciator modules
- Generator temperature monitoring
- Auxiliary box
- Remote speed adjust
- Busbar connections
- Vandal proof panel door
- Voltage raise/lower switch
- EMCP 4.3, EMCP 4.4
- Local and remote monitoring
- Language options
- Customer interface options
- External box clips
- EMAX breaker connections
- Governors
- Cooling System
-
- Heat exchangers
- Water level switch gauges
- Radiator duct flanges
- Optional Serpentine radiators
- European Certifications
-
- EU Declaration of Conformity
- Exhaust System
-
- Through wall installation kit
- Muffler mounting kits
- Mufflers
- Flexible fittings
- Fuel System
-
- Fuel coolers
- Primary fuel filter
- Generators And Attachments
-
- Generators
- 3 Phase, Random wound, Internal excitation (IE)
- Internal excitation (IE)
- 3 Phase, 380 / 400 / 415 / 3300 / 6600 / 10000 / 10500 / 11000 volt
- Number of leads: 6
- Pitch: 0.6667
- Instrumentation
-
- Pyrometers and thermocouples
- Thermocouples
- Lube System
-
- Oil level regulator
- Electric prelube pumps
- Manual prelube sump pumps
- Mounting System
-
- IBC vibration isolators
- Spring type vibration isolators
- Special Tests / Reports
-
- IBC seismic Certification
- CSA test and certification
- PGS Test report @ 1.0 power factor
- Neutral ground certificate
- PGS Test report @ 0.8 power factor
- Starting / Charging System
-
- 10 and 20 Amp Battery chargers
- Charging alternators - 50 Amp
- Dual 24 volt electric starting motors
- ETHER starting aids
- 24 Volt battery set - Dry
- Jacket water heaters