3516E Low Voltage Generator Set

3516E Low Voltage Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

PDF Print Share

Generator Set Specifications

Standby Rating
3000 ekW
Prime Power Rating
2725 ekW
Emissions/Fuel Strategy
Tier 2
Voltage
416 to 13,800 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime
Maximum Rating
3000 ekW
Minimum Rating
2725 ekW

Engine Specifications

Engine Model
3516E, V-16, 4-Stroke, Water-Cooled Diesel
Bore
6.69in
Stroke
8.47in
Displacement
4765in³
Compression Ratio
13.9:1 / 14.3:1
Aspiration
ATAAC
Fuel System
MEUI
Governor Type
Adem™ A5

Generator Set Dimensions

Length - Maximum
304in
Width - Maximum
113in
Height - Maximum
143in
Dry Weight - Genset (maximum)
44930lb

Standard Equipment:

Optional Equipment:

    Air Inlet System
    • Air inlet protection
    • Remote air inlet adapters
    • Heavy duty air cleaners
    • Dual element air cleaners
    Circuit Breakers
    • 2000, 2500, 3200, 4000 Amp, 4 Pole, IEC rated Circuit breakers
    • Circuit breaker harnesses
    • Masterpact breaker connections
    • P Frame breaker connections
    • 2000, 2500, 3200, 4000, 5000 Amp, 3 Pole, IEC rated Circuit breakers
    • Busbar connections
    • R Frame breaker connections
    • Cable entry options
    • 1600, 2000, 2500, 3000, 4000, 5000 Amp, 3 Pole, UL-100% rated Circuit breakers
    • Optional busbar power connections
    Power Termination
    • Circuit breakers, IEC compliant
    Control Panel
    • Voltage raise/lower switch
    • PC monitoring (Remote and local)
    • Generator temperature monitoring
    • Remote speed adjust
    • Annunciator modules
    • EMCP 4.4
    • Vandal proof panel door
    • Auxiliary box
    • Customer interface options
    • Ground
    • Language options
    • Load share module options
    • Mounting group - External box clips
    Cooling System
    • Optional Serpentine radiators
    • Optional ATAAC radiators
    • Water level switch gauges
    • Expansion tanks
    Exhaust System
    • Flexible fittings
    • Y Adapters
    • Elbows
    • Mufflers
    • Flanges
    • Flanges and exhaust fittings
    Fuel System
    • Duplex fuel filters
    • Primary fuel filters
    Generators And Attachments
    • Differential current transformers - 8.7 and 15 kV class
    • Alternator air cleaners
    Instrumentation
    • Pyrometer and thermocouples
    Lube System
    • Manual prelube pump
    • Electric prelube pumps
    • Oil level regulator
    • Lube oil in standard sump
    Mounting System
    • Spring type vibration isolators
    • IBC Seismic vibration isolators NORAD
    • Puck style low efficiency lsolators
    Power Connections
    • Neutral ground connections
    • 2700 & 3000 Frame
    • Grounding groups
    Special Tests / Reports
    • Fuel consumption test
    • Torsional vibration analysis
    • Standard engine test charge
    • IBC Certifications
    • Generator set consumption test
    • Generator set test report
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
    Starting / Charging System
    • Engine barring group
    • 10, 20, 35 and 50 Amp Battery chargers
    • Starter cover
    • Jacket water heaters
    • 24 Volt battery set - Dry
    • Electric starting motors
    • Air starting motors
    • Air pressure regulator
    General
    • US aid emblem
    • Special paint colors