C32 | 1250 kVA 50 Hz Generator Set
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.Producing reliable power from 910 kVA to 1500 kVA at 50 Hz,
... our C32 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Generator sets range from low fuel consumption to low emissions systems. Seismic certification is also available for select models, ensuring you maintain power after unexpected disturbances. Our integrated control system, including ATS and switchgear, protects your power supply and keeps you connected through on-site and remote monitoring options. We offer easy-to-use EMCP control panel options, combining your management and diagnostic tools in one. The EMCP 4.4 controller provides multi-generator set paralleling capability, giving you the ability to add generator sets to match your growing power requirements. Browse a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging to fit unique spatial requirements and environmental conditions. Our C32 generator sets are made for demands, so you can make yours.
Generator Set Specifications
- Maximum Rating
-
1500 kVA
- Minimum Rating
-
910 kVA
- Emissions/Fuel Strategy
-
Low Fuel, Low Emissions
- Voltage
-
400 to 3300 Volts
- Frequency
-
50 Hz
- Speed
-
1500 rpm
- Duty Cycle
-
Standby, Mission Critical, Prime, Continuous
Engine Specifications
- Engine Model
-
C32 TA, V-12, 4-Stroke Water-Cooled Diesel
- Bore
-
5.71in
- Stroke
-
6.38in
- Displacement
-
1958.86in³
- Compression Ratio
-
15.0:1
- Aspiration
-
Turbocharged, Air to Air Aftercooled
- Fuel System
-
MEUI
- Governor Type
-
Adem™A4
Generator Set Dimensions
- Length - Minimum
-
164in
- Length - Maximum
-
176.6in
- Width - Minimum
-
66.3in
- Width - Maximum
-
87.8in
- Height - Minimum
-
85.1in
- Height - Maximum
-
86.4in
- Dry Weight - Genset (minimum)
-
14700lb
- Dry Weight - Genset (maximum)
-
17855lb
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR500 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
EMCP 4 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- EU Declaration of Conformity
- EU Declaration of Incorporation
- Eurasian Conformity (EAC)
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment:
- Air Inlet System
-
- Single element canister type with service indicator
- Control Panel
-
- GCCP Control panel
- Control features
- Programmable protective relaying functions
- Digital indicators
- Warning shutdowns
- Communications
- Cooling System
-
- Fan and belt guards
- Radiator fan and fan drive
- ATAAC
- Coolant drain line with valve
- Caterpillar extended life coolant
- Low coolant level sensor
- Exhaust
-
- Exhaust manifold - dry
- 203 mm (8 in) ID round flanged outlet
- Fuel System
-
- Primary fuel filter with water separator
- Fuel priming pump
- Secondary fuel filters
- Fuel cooler
- Generators And Attachments
-
- Integrated voltage regulator (IVR)
- Permanent magnet excitation (PMG)
- 3 Phase brushless
- Reactive droop
- Internal excitation (IE)
- NEMA Class H insulation
- Class H temperature rise at 40C ambient
- Salient pole
- Winding temperature detectors
- 6 Lead
- IEC standard hole pattern
- Busbar connections, top center mounted, top cable entry
- Mounting System
-
- Rails - engine/generator/radiator mounting
- Rubber anti-vibration mounts
- Lube System
-
- Oil drain lines and valve
- Integral lube Oil cooler
- Fumes disposal
- Lubricating oil
- Oil filter, filler and dipstick
- Gear type lube oil pump
- Starting / Charging System
-
- 24 Volt electric starting motor
- Battery, rack and cables
- Battery disconnect switch
- 45 Amp Charging alternator
- General
-
- Caterpillar yellow with high gloss black rails & radiator
- RH service
- Flywheel and flywheel housing-SAE
- SAE standard rotation
Optional Equipment:
- Air Inlet System
-
- Dual element air cleaner
- Heavy duty air cleaner
- Standard air cleaners
- Circuit Breakers
-
- 1600, 2000, 2500 and 3200 Amp, 3 Pole, IEC-Rated Circuit breakers
- Enclosures - Control packaging
- Cable supports
- Center posts busbars
- Circuit breaker wiring groups
- Power connection covers
- Shrouds
- 400, 800, 1200, 1600, 2000, 2500 and 3000 Amp, 3 Pole, UL-100% Rated Circuit breakers
- 800, 1600, 2000, 2500 and 3200 Amp, 4 Pole, IEC rated Circuit breakers
- Cooling System
-
- Radiator duct flange
- Certified radiator
- High ambient radiator
- Standard radiator
- Extended life coolant
- Enclosures
-
- Enclosure fuel tank options
- Sound attenuated enclosure
- Enclosure louvres - fixed and motorized
- Color options
- AC Panel, outlets and lights
- Premium sound attenuated enclosure
- Cold weather bundle
- Panel bracket
- DC lighting package
- Exhaust System
-
- Exhaust through the wall kit
- Flange and exhaust expanders
- Flanges
- Guard and shield system
- All C32 engines have 203 mm (8 in) exhaust outlets
- Elbow mounting kit
- Mufflers
- Flexible fittings
- Generator And Attachments
-
- Low voltage generators
- Medium voltage generators
- Lube System
-
- Oil pan
- Prelube manual sump pump
- Oil level regulator
- Mounting System
-
- IBC vibration isolators
- Mounting base types
- Spring type vibration isolators
- Standard package isolators
- Power Termination
-
- Circuit breakers, IEC compliant
- Circuit breakers, UL listed
- Power Connections
-
- Low voltage connection cables
- Neutral grounding connection
- Center post busbars
- Starting / Charging System
-
- 10 Amp enclosure Battery charger
- Space heater
- 10 Amp Battery charger
- 20 Amp Battery charger
- 35 Amp Battery charger
- Electric starting motor - Standard/heavy duty
- Standard 24 volt open package battery set - Dry
- Jacket water heater
- Special Tests / Reports
-
- PGS Test report @ 1.0 power factor
- Standard engine test
- Generator test report
- Custom generator TVA report
- PGS Test report @ 0.8 power factor
- CSA test and certification
- IBC seismic Certifications
- Standard genset Torsional Vibration Analysis (TVA) report
- OSHPD seismic Certifications
- General
-
- Special paint
- US aid emblem