Cat® CBS – ATS with Bypass Isolation (Spec Grade)
The CBS Series – Open Transition, Delayed Transition (CBSD), Closed Transition (CBSCT), ATS with Bypass Isolationis is equipped with an intuitive full-color touchscreen HMI and is compatible with Ekip Connect ...
Technical Summary
- Rating Range
- 100 - 3000 A
- Transfer Type
- Open Transition (CBS), Delayed Transition (CBSD), Closed Transition (CBSCT), with Bypass Isolation
- Switch Type
- Contactor
System Information
- Product nodes
- UL: Open transition 100-3000A, Delayed transition 100-3000A, Closed transition 1000-3000A
- Rated Voltage and Frequency
- 200-480VAC, 50/60 Hz
- Phase system
- Single and Three
- Number of poles
- 2, 3 and 4
- Neutral configuration
- Solid neutral, Switched neutral, Overlapping neutral (100-1200A only)
- Product type
- Open transition (I-II), Delayed Transition (I-O-II), Closed transition (I-O-II)
Product Features
- Advanced safety with faster switching and no line voltages connected at the door
- Voltage and frequency sensing of both sources and load
- USB port to upload/download settings
- Available Bluetooth connection and enhanced communication capabilities
- Password protection color touchscreen HMI
- Integrated help button and menu
- Five programmed packages and IO
- Contact wear monitoring including real-time status and predicted contact end-of-life
- Fast controller response to outage recovery and fast switching (<50ms)
Control Panel
- TruOne L4 - color touchscreen HMI compatible with Ekip Connect software, with standard programmable functions and IO, and fast controller response to outage recovery and fast switching (<50ms).
Functions
- High current protection and alarm
- Wide 200-480V range with auto-configuration of system settings for 100-1200A range
- High time-based withstand and closing ratings (WCR)
- Short-time withstand ratings in every frame (CBS, CBSD, and CBSCT models)
Standards
- UL 1008, NFPA 70, 99, 101 and 110
- NEMA ICS 10
- cUL
- Conducted and radiated emissions - CISPR 11:2009, Class A
- ESD immunity test - IEC/EN 61000-4-2 Class B
- Radiated RF, electromagnetic field immunity test - IEC/EN 61000-4-3 10 V/m
- Electrical fast, transient/burst immunity test - IEC/EN 61000-4-4
- Surge immunity test - IEC/EN 61000-4-5 0.5 to 2 kV
- Conducted immunity test - IEC/EN 61000-4-6
- Voltage dips and interruption immunity - IEC/EN 61000-4-11
- Harmonic voltage immunity test - IEC/EN 6100-4-13