Rating Range
30 - 3000 A
Transfer Type
Open Transition (CS), Delayed Transition (CSD), Closed Transition (CSCT)
Switch Type
Contactor

System Information

Product nodes
UL: 30-200 A, 260-1200 A, 1600-3000 A
Rated Voltage and Frequency
200-480VAC, 50/60 Hz
Phase system
Single and Three
Number of poles
2, 3 and 4
Neutral configuration
Solid neutral, Switched neutral, (Optional) Overlapping neutral
Product type
Open transition (I-II), Delayed Transition (I-O-II), Closed transition (I-O-II) 1600-3000A only

Product Feature

        

  • Voltage and frequency sensing of both sources and load
  •     

  • USB port to upload/download settings
  •     

  • Available Bluetooth connection and enhanced communication capabilities
  •     

  • Password protection color touchscreen HMI
  •     

  • Integrated help button and menu
  •     

  • Five programmed packages and IO
  •     

  • Contact wear monitoring including real-time status and predicted contact end-of-life (30-1200A only)
  •     

  • Fast controller response to outage recovery and fast switching (<50ms)

Control Panel

        

  •     
  •     

  • TruOne L4 - color touchscreen HMI compatible with Ekip Connect software, with standard programmable functions and IO, and fast controller response to outage recovery and fast switching (<50ms).

Functions

        

  • High current protection and alarm
  •     

  • Wide 200-480V range with auto-configuration of system settings for 30-1200A range
  •     

  • High time-based withstand and closing ratings (WCR)
  •     

  • Short-time withstand ratings in every frame (CS, CSD, and CSCT models)

Standards

        

  •     
  •     

  • UL 1008, NFPA 70, 99, 101 and 110
  •     

  •     
  •     

  • NEMA ICS 10
  •     

  •     
  •     

  • cUL
  •     

  •     
  •     

  • Conducted and radiated emissions - CISPR 11:2009, Class A
  •     

  •     
  •     

  • ESD immunity test - IEC/EN 61000-4-2 Class B
  •     

  •     
  •     

  • Radiated RF, electromagnetic field immunity test - IEC/EN 61000-4-3 10 V/m
  •     

  •     
  •     

  • Electrical fast, transient/burst immunity test - IEC/EN 61000-4-4
  •     

  •     
  •     

  • Surge immunity test - IEC/EN 61000-4-5 0.5 to 2 kV
  •     

  •     
  •     

  • Conducted immunity test - IEC/EN 61000-4-6
  •     

  •     
  •     

  • Voltage dips and interruption immunity - IEC/EN 61000-4-11
  •     

  •     
  •     

  • Harmonic voltage immunity test - IEC/EN 6100-4-13

Standard Equipment:

Optional Equipment:

    Optional Neutral Configuration
    • Overlapping neutral