Cat XLM Switchgear
The Emergency Transfer and Load management (XLM) product supports transfer between the utility source and generator bus and allows for sustained parallel operation with the utility for load management applications. ...
Technical Summary
- Configuration
- Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
- Modes of Operation
- Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
- Application
- LV and MV ( 208V - 38 kV
Generator Protective Devices
- ANSI Protective Devices
- 15/25, 27/59, 81 O/U, 32, 40, 50, 51
Utility Protective Devices
- ANSI Protective Devices
- 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86
Environmental Parameters
- Certifications
- IBS, CBC, UBC & OSHPD Certified
- Control Panel Enclosure
- NEMA 1 or NEMA 3R, Freestanding Construction
- Operating Temperature
- 0 degrees to 50 degrees C
- Storage Temperature
- -20 degrees C to +60 degrees C
- Low Voltage Standards
- NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
- Medium Voltage Standards
- NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
XLM Switchgear
- High Speed Supervisory Network
- Automatic Start/Stop
- Automatic “Dead Bus” Coordination
- Automatic Power Factor Control when in Parallel with Utility Power
- Programmable Load Shed / Load Add Functions
- Networked Engine Communications
- Generator & Utility Protection
- Engine Tuning
- Mode Selection
- Selectable Auto/ Manual Control
- Password Protection for Protective Settings and Setup
- Load/No Load Test
- Touch Screen (HMI) Display
- NFPA 99/110 Compliant Alarm
- Annunciation with Audible Horn
- Engine Control mimic Screen with gauges for RPM, DC Battery Voltage, Oil Pressure, Engine Coolant temperature, Engine Hours, Number of starts